Case study · Commercial EICR

Commercial EICR in Highfield, Sheffield S2

Comprehensive electrical inspection of commercial premises in Sheffield

UnsatisfactoryHighfield, Sheffield S2Commercial premisesTwo engineers

Location

Highfield, Sheffield S2

Property

Commercial premises

Inspection

Two engineers, full working day

EICR result

Unsatisfactory

Browse case studies and guides

Sheffield EICR recently carried out a comprehensive commercial Electrical Installation Condition Report (EICR) at business premises in Highfield, Sheffield S2.

The premises contained a more complex electrical installation than a typical domestic property, with multiple distribution boards supplying offices, IT and connectivity areas, staff facilities, lighting, kitchen equipment and other electrical equipment.

The inspection was carried out by two engineers over the course of the working day and involved detailed inspection and testing of the existing electrical installation.

The resulting EICR was Unsatisfactory, identifying a number of electrical defects and areas requiring improvement.

What did the commercial EICR find?

Inspection and testing revealed signs of ageing and previous poor-quality electrical work, particularly in areas concealed above the suspended ceilings.

Some of the significant findings included:

Finding 1

Multiple circuits without RCD protection

Including socket circuits, kitchen equipment and a lighting circuit serving the shower-room area.

Finding 2

An open-circuit fault on a large ring final circuit

The circuit supplied approximately 27 socket outlets across several areas of the premises and required investigation and repair.

Finding 3

Poor-quality electrical connections above suspended ceilings

Including taped connections and other terminations requiring proper electrical enclosures and connectors.

Finding 4

Incorrect circuit arrangements serving hand dryers

Two radial circuits had been terminated into a single 32A circuit and required separate appropriate protection.

Finding 5

Missing main protective bonding to the gas service

Requiring installation of the appropriate bonding conductor.

Further observations included exposed cabling where trunking lids were missing, poor lighting connections, a failing and overheating shower-room light, missing earth sleeving and a lighting point without an earth conductor.

Why commercial EICRs need thorough inspection

Commercial electrical installations often develop over many years.

Additional sockets are installed, offices are rearranged, equipment changes and electrical circuits can be altered by different contractors at different times.

From ground level, much of the installation can appear perfectly normal.

However, this inspection demonstrated why proper testing—and inspection of accessible areas above suspended ceilings—can be so important.

Several of the problems discovered weren’t simply visible accessories requiring replacement. They involved the underlying circuit arrangements, electrical connections and protective measures serving the building.

One circuit was serving around 27 socket outlets

One particularly important finding involved a large ring final circuit supplying approximately 27 socket outlets across the kitchen, core room, staff dining area and software room.

Testing identified a continuity fault/open circuit on this circuit.

Rather than simply repairing the immediate fault and leaving the existing arrangement unchanged, our recommendation was to investigate the circuit and consider dividing it into separate circuits.

This could provide a more appropriate arrangement for the different areas of the business while improving the resilience and maintainability of the installation.

RCD protection across the premises

The inspection also identified numerous circuits without additional RCD protection.

These included socket outlets within office areas, kitchen circuits, oven and hob supplies and a lighting circuit serving an area containing a shower.

The remedial recommendations therefore included upgrading the relevant circuit protection using suitable RCBOs, subject to compatibility with the existing distribution equipment and final circuit verification.

Clear advice after the inspection

With a commercial EICR containing numerous observations, simply handing the customer a technical certificate isn’t particularly helpful.

Our role is to establish

Following completion of this EICR, the customer asked Sheffield EICR to provide a quotation for the necessary remedial work.

They specifically requested that the C2 defects and C3 recommendations were identified separately, allowing the different priorities to be clearly understood.

This separation is important.

Not every observation on an EICR carries the same level of urgency, and businesses and landlords should be able to understand the difference when planning remedial electrical work.

Planning remedial work around a working business

Commercial electrical remedial work also requires consideration of how the premises are actually used.

Some electrical work can be completed during normal business hours.

Other work may require circuits or sections of the installation to be isolated, potentially disrupting staff, IT systems or normal business operations.

Our subsequent remedial proposal therefore considered completing non-disruptive work during normal hours and scheduling work requiring more significant isolation outside normal operating hours where necessary.

It’s not simply about identifying electrical defects. It’s about finding a practical way to rectify them.

Commercial EICRs in Sheffield

Sheffield EICR provides commercial EICRs in Sheffield for offices, shops, workplaces and other business premises.

Our electrical inspections include comprehensive testing of the existing installation, clear documentation of any defects identified and practical advice about the next steps.

Where remedial electrical work is required, this is quoted separately following the inspection.

Whether we’re inspecting a house, rental property or complex commercial premises, the objective is the same—to provide an independent assessment of the electrical installation and explain the findings clearly.

Case summary

LocationHighfield, Sheffield

Postcode areaS2

PropertyCommercial premises

ServiceCommercial Electrical Installation Condition Report (EICR)

InspectionTwo engineers, comprehensive inspection and testing

EICR resultUnsatisfactory

Key findingsRCD protection, circuit continuity fault, poor electrical connections, circuit arrangements and protective bonding

Follow-upSeparate remedial quotation with C2 and C3 works clearly identified

Need a commercial EICR?

We’ll plan the inspection around your business and explain every finding clearly.

Or call 0330 043 2031

Our approach

Inspect → Explain → Advise

Our approach to this commercial inspection, and every inspection we carry out.

1

Inspect

Two engineers inspected and tested the installation, including accessible areas above the suspended ceilings.

2

Explain

Every finding was documented clearly, with C2 defects and C3 recommendations identified separately.

3

Advise

Remedial work was quoted separately, with disruptive work planned outside normal operating hours where necessary.

Helping you make confident electrical decisions